Old System

Electric baseboard radiators, electric hot water tank, 7.6 LPF toilets

New System

LG multi-split cold climate air source heat pumps, Rheem Air Source domestic hot water heat pumps, and low flow toilet retrofit.

Partners

Toronto Community Housing Corp. | Ecosystem

Download Report

Project Details

66 Walpole Ave, Toronto: Town house complex, owned by Toronto Community Housing Corporation

Old System: Electric baseboard radiators, electric hot water tank, 7.6 LPF toilets

New System: LG multi-split cold climate air source heat pumps, Rheem Air Source domestic hot water heat pumps, and low flow toilet retrofit.

Partners: Toronto Community Housing Corp. | Ecosystem


March 2023. City of Mississauga. In August 2020, TAF’s Retrofit Accelerator team joined project partners to retrofit a 12-storey 1965 apartment building in Mississauga, Ontario. The building had recently completed an LED lighting system upgrade, and we aimed to further reduce energy consumption and emissions by introducing energy-efficient heating and cooling, leading to a 27% overall reduction.



Recommendations

  • Create a mock installation to test new technologies.

    Understanding sequencing and interaction of trades, and troubleshooting issues without disrupting residents prior to a full building rollout improves results and resident satisfaction.

  • Enable cooling

    to increase resident comfort and satisfaction, reduce peak demand, and protect against health impacts of extreme heat.

  • Lengthen cycle times and reduce return temperatures to allow GAHP to reach maximal steady-state efficiency.

    Increase the deadband of the GAHP controller to keep it on for longer periods, installing the heat exchanger in a counterflow configuration to promote better heat transfer (and likely reduce the temperatures in the GAHP glycol loop). And, add more intelligent control to the recirculation loop such that it is not unnecessarily mixing hot water with the cold city water prior to the GAHP heat exchanger.

22%

reduction in greenhouse gas emissions

$5k

annual savings on energy bills

100%

tenant satisfaction with thermal comfort

17%

reduction in electricity demand